Applying 440.22(B)(1) to the 10 ton rooftop unit, the MOCP calculation looks like this:
The calculated MOCP for the rooftop unit becomes 76.4 amps, making a 70 amp fuse or breaker a suitable choice.
Occasionally, the manufacturer's catalog or the equipment nameplate will say "Maximum Fuse Size" instead of "Maximum Overcurrent Protection" or "MOCP." In that case, unless there is a footnote that allows a circuit breaker, the MOCP must be a fuse.