NMBE = 100 x[([summation](yi-[??]i))/(n-1)]/[bar.y] (2)
The CV-RMSE and NMBE for the total floor after the calibration was 24.8% for CV-RMSE and 8.6% for NMBE, which were within the tolerance range specified in ASHRAE Guideline 14 (i.e., 30% CV-RMSE and 10% NMBE for hourly data) (ASHRAE 2014).
CV-RMSE and NMBE Values for the Initial Energy Simulation Comparison CV-RMSE NMBE Total floor 37.4% -5.7% VRF outdoor unit 74.0% 27.8% VRF indoor units 88.9% 85.1% DOAS 47.6% 8.3% Indoor lighting 102.6% -95.3% Plug loads 123.2% -121.3% Table 3.